Oral topic27 min readJump to 35 questions

Refrigeration and air conditioning oral questions and model answers for marine engineers

Refrigeration orals test the vapour compression cycle, each safety cut-out, and fault-finding: high head pressure, short cycling, moisture, oil return and leaks. Examiners also ask about MARPOL Annex VI Reg. 12 on ozone-depleting refrigerants and safe response to a refrigerant leak.

On this page
  1. Key facts
  2. What do examiners ask about refrigeration at each rank?
  3. How does the vapour compression cycle work on a ship?
  4. What do MARPOL rules say about refrigerants?
  5. How do you fault-find a refrigeration plant from gauge readings?
  6. What do you do if there is a refrigerant leak in a closed space?
  7. What extra safety rules apply to ammonia refrigeration?
  8. How should you structure a refrigeration answer in the oral?
  9. What mistakes do candidates make on refrigeration?
  10. What do examiners ask about ship air conditioning?
  11. How do you calculate superheat and subcooling on a refrigeration plant?
  12. How do you walk through a refrigeration breakdown in the oral?
  13. What should you read to revise refrigeration and air conditioning?
  14. How can you practise refrigeration answers before the oral?
  15. 35 practice questions
  16. Frequently asked questions
  17. Sources

Key facts

Main cycle
Vapour compression: compressor, condenser, expansion valve, evaporator
Environmental rule
MARPOL Annex VI Reg. 12 (ozone-depleting substances)
Non-HCFC ODS banned
New installations on ships built on or after 19 May 2005[1]
HCFC (e.g. R22) banned
New installations from 1 January 2020[1]
Record keeping
ODS Record Book for rechargeable systems[1]
Ammonia plants
Dedicated gastight room, 30 air changes per hour, detectors (IACS UR M57)[2]
Examined at
MEO Class 4, 2 and 1; MCA EOOW, Second and Chief Engineer orals
Practice set
Refrigeration MCQ bank with explanations

Checked 13 November 2026. Fees and rules change: confirm with the authority before you book.

What do examiners ask about refrigeration at each rank?

Refrigeration is part of Marine Engineering at operational and management level. At MEO Class 4 and the MCA EOOW oral you must explain the cycle, the safety cut-outs and day-to-day faults. At MEO Class 2, MEO Class 1, the MCA Second Engineer oral and the MCA Chief Engineer oral the questions move to refrigerant regulations, plant performance, overhaul, and safety management of leaks. India's engine grades map to STCW III/1 and III/2[3]; the UK engineering oral syllabus is MIN 654[4].

Depth expected on refrigeration and air conditioning by exam
ExamLevelWhat they usually probe
India MEO Class 4Operational (III/1)Cycle with a sketch, components, cut-outs, charging and purging, defrosting, common faults, leak detection
India MEO Class 2Management, second engineerSuperheat and subcooling, TEV setting, compressor overhaul, capacity control, oil return, refrigerant change-over
India MEO Class 1Management, chief engineerMARPOL Annex VI Reg. 12, ODS Record Book, refrigerant phase-down, ammonia safety, reefer cargo claims, energy efficiency
MCA EOOWOperationalScenarios: high pressure trip on the provision plant at night, room temperature rising, leak alarm
MCA Second EngineerManagementFault-finding from gauge readings, plant overhaul, air conditioning balance and humidity
MCA Chief EngineerManagementCompliance, crew safety in refrigerant leaks, planning maintenance and spares

How does the vapour compression cycle work on a ship?

The refrigerant absorbs heat in the evaporator by boiling at low pressure, is compressed to high pressure and temperature, rejects heat in the condenser to sea water or fresh water cooling, and passes through an expansion valve back to the evaporator. Learn it with the state of the refrigerant at each point; examiners often ask you to draw it and mark pressures and temperatures.

Main components and what to say about each
ComponentJobWhat the examiner wants to hear
CompressorRaises pressure and temperature of the vapourReciprocating or screw; oil lubrication; capacity control by unloading cylinders or slide valve
Oil separatorReturns oil carried over to the compressor crankcaseImportant for oil return and evaporator efficiency
CondenserRejects heat; vapour condenses to liquidShell-and-tube, sea water cooled; non-condensables collect here; relief valve
ReceiverStores liquid refrigerantAllows pump-down; liquid level sight glass
Filter drierRemoves moisture and dirtChange if moisture indicator shows wet or there is a pressure drop across it
Solenoid valveOpens or closes liquid supply to a roomControlled by room thermostat
Thermostatic expansion valveDrops pressure and meters liquid to keep a set superheatBulb on evaporator outlet; equaliser line on large evaporators
EvaporatorRefrigerant boils and absorbs heat from the room airFans; frost builds up and needs defrosting
Safety cut-outsProtect the plantHP cut-out, LP cut-out, oil pressure differential cut-out, cooling water failure, motor overload

What do MARPOL rules say about refrigerants?

MARPOL Annex VI Regulation 12 controls ozone-depleting substances (ODS) on ships. Deliberate emissions of ODS are prohibited. New installations containing ODS other than HCFCs have been banned on ships built on or after 19 May 2005, and new installations containing HCFCs such as R22 from 1 January 2020[1]. Ships keep a list of equipment containing ODS and, for rechargeable systems, an ODS Record Book in which recharges, repairs, discharges and deliveries to shore are recorded in kilograms[1]. Permanently sealed units with no charging connections are outside the regulation.

HFC refrigerants such as R134a, R404A, R407C and R507 do not deplete ozone, so they are not ODS under Reg. 12, but they have high global warming potential. They are being phased down under the Kigali Amendment to the Montreal Protocol and regional rules, so ships increasingly use lower-GWP refrigerants or natural refrigerants such as ammonia or CO2. Ammonia plants have their own class rules (see below). The MARPOL oral topic and the fuel sulphur rules and scrubbers page cover the rest of Annex VI.

How do you fault-find a refrigeration plant from gauge readings?

Examiners give you symptoms and expect a reasoned list of causes. Typical patterns are below; the right values for your plant come from the maker's manual and the log of normal readings.

Common symptoms and likely causes
SymptomLikely causesFirst checks
High discharge (head) pressureAir or other non-condensables, dirty or fouled condenser tubes, low cooling water flow or high sea temperature, overchargeCooling water pump and valves, condenser temperature difference, purge non-condensables
Low suction pressureUndercharge (leak), choked filter drier or strainer, iced evaporator, TEV fault or lost bulb charge, solenoid not openingSight glass for bubbles, frost on drier, defrost state, TEV superheat
High suction pressureCompressor valves leaking, TEV overfeeding, high room load (door open, warm cargo)Compressor discharge temperature, room doors, TEV bulb position
Short cyclingLP cut-out differential too narrow, undercharge, leaking solenoid valve, HP cut-out acting from poor condenser coolingCut-out settings, charge, condenser
Bubbles in liquid sight glassUndercharge or flash gas from pressure drop before the glassLeak test, drier pressure drop
Ice at the expansion valve, plant stops coolingMoisture freezing at the orificeChange drier, evacuate if needed
Oil level falling in compressorOil trapped in evaporator, failed oil separator float, long off cyclesOil separator, suction line slopes, defrost

What do you do if there is a refrigerant leak in a closed space?

A large leak in a plant room or cold room can displace oxygen, and some refrigerants are toxic. Treat it as an enclosed space hazard and never rush in. The steps below are the general principle; follow the ship's emergency plan.

  1. 1
    Raise the alarm and keep people out

    Inform the bridge and chief engineer. Nobody enters the space without breathing apparatus and a rescue team standing by.

  2. 2
    Stop the plant and isolate

    Stop the compressor from outside if possible and close the king valve or isolating valves to limit the loss.

  3. 3
    Ventilate

    Run exhaust ventilation from outside. Halocarbon refrigerants are heavier than air and collect low down; ammonia rises and is toxic and corrosive.

  4. 4
    Remove ignition and heat sources

    Halocarbon refrigerants break down in flame or on hot surfaces into toxic gases; ammonia is flammable in a range of concentrations. No hot work or naked lights.

  5. 5
    Enter only when safe

    Test the atmosphere for oxygen and the refrigerant, enter with breathing apparatus if needed, find and fix the leak.

  6. 6
    Record

    Record the loss and recharge in the ODS Record Book if the refrigerant is an ODS, or in the plant records, and report under the SMS.

What extra safety rules apply to ammonia refrigeration?

Ammonia (R717) is efficient and has no ozone depletion, but it is toxic, corrosive and flammable in some concentrations. IACS UR M57 requires ammonia machinery to be in a dedicated gastight compartment with at least two access doors (except small rooms), independent negative ventilation of at least 30 air changes per hour, fixed ammonia detection with alarms inside and outside, water screens over the doors operable from outside, an independent bilge system, at least two sets of breathing apparatus and protective clothing, and no ammonia piping through accommodation[2]. Water absorbs ammonia, which is why water screens and spray are used. For gas leaks and fire, also read the fire-fighting oral topic and emergency procedures.

How should you structure a refrigeration answer in the oral?

Draw first, talk second. Sketch the cycle with the compressor, condenser, receiver, drier, solenoid, expansion valve and evaporator, then mark high and low pressure sides. For a fault: state the symptom, the two or three most likely causes, the readings you would check to tell them apart, and the fix.

Use correct terms: superheat (vapour temperature above its saturation temperature at that pressure), subcooling (liquid below its saturation temperature), non-condensables, flash gas. The mock oral drill is a good way to practise talking through a sketch, and what oral examiners look for explains how marks are given.

What mistakes do candidates make on refrigeration?

  • Saying the expansion valve controls room temperature. It controls superheat at the evaporator outlet; the thermostat and solenoid control room temperature.
  • Saying R134a or R404A is banned under MARPOL Annex VI Reg. 12. They are HFCs, not ODS.
  • Using oxygen or compressed air to pressure test a system. Use dry nitrogen.
  • Charging a zeotropic blend such as R407C as vapour from the cylinder top, which changes its composition.
  • Venting refrigerant to atmosphere to clear air. Recover it.
  • Forgetting the ODS Record Book for R22 plants still in service.
  • Saying a halide lamp finds HFC leaks. It works on chlorine-containing refrigerants only.

See why seafarers fail oral exams for wider patterns.

What do examiners ask about ship air conditioning?

Air conditioning controls temperature, humidity, air movement and air quality in the accommodation. A central air handling unit mixes fresh air with recirculated air, filters it, cools and dehumidifies it on a cooling coil (direct expansion or chilled water), heats it with steam, hot water or electric heaters, and in winter adds moisture with a humidifier.

  • Summer: cooling coil below the dew point removes moisture; reheat may be used for comfort.
  • Winter: preheat, humidify, then heat.
  • Control: thermostats and humidistats; dampers set fresh air ratio; fire dampers close on fire.
  • Hygiene: clean drip trays and drains, clean filters, control Legionella in humidifiers and water systems.
  • Faults: room too warm (low refrigerant, dirty coil, fan belt, damper position), high humidity (cooling coil not cold enough, too much fresh air), smells (dirty drip tray, blocked drain).

See also marine electrical systems for fan motors and starters.

How do you calculate superheat and subcooling on a refrigeration plant?

Superheat is the evaporator outlet temperature minus the saturation temperature at the evaporator (suction) pressure. Subcooling is the saturation temperature at condensing pressure minus the actual liquid line temperature. You read the saturation temperatures from the pressure–temperature (PT) chart for the refrigerant in use.

Worked example (example figures). A provision plant is running on its cold room.

  1. The suction pressure gauge reads a pressure whose saturation temperature on the PT chart for the plant's refrigerant is −8 °C.
  2. A contact thermometer on the suction line at the evaporator outlet, next to the TEV bulb, reads −2 °C.
  3. Superheat = −2 − (−8) = 6 K.
  4. The condenser pressure gauge reads a pressure whose saturation temperature on the chart is 38 °C. The liquid line after the condenser reads 33 °C.
  5. Subcooling = 38 − 33 = 5 K.

Compare the results with the maker's settings and your normal log readings, not with a number from memory. Gauges on many ships show more than one refrigerant scale; read the scale for the gas actually in the plant. For zeotropic blends such as R407C, use the dew point for superheat and the bubble point for subcooling.

What the numbers tell you.

Reading superheat and subcooling together
SuperheatSubcoolingSuction pressureMost likely cause
HighLowLowUndercharge (leak); bubbles in the sight glass
HighNormal or highLowRestriction before the evaporator: choked drier, iced TEV orifice, TEV bulb charge lost
LowNormalHighTEV overfeeding (bulb loose or badly placed); risk of liquid flood-back to the compressor
NormalHighNormal or highOvercharge, or liquid backing up in the condenser
NormalLowHigh head pressureAir or other non-condensables in the condenser

How do you walk through a refrigeration breakdown in the oral?

Protect the cargo or provisions, then the compressor: keep room doors shut, find the cause from pressures and superheat, and never bypass a cut-out. Two walk-throughs follow.

Walk-through 1: cold room temperature rising, compressor running

Symptom. The meat room is warming slowly. The compressor runs continuously; suction pressure is lower than usual.

Checks in order.

  1. Room door seals and door left open; curtain or heater faults.
  2. Evaporator coil: is it iced up? A failed defrost heater, timer or drain heater leaves the coil blocked with ice and the room warms while suction pressure falls.
  3. Room solenoid valve: is it opening? Check the coil and the thermostat signal.
  4. Sight glass and superheat (see above): bubbles and high superheat mean undercharge or a restriction.
  5. Filter drier: frost or a temperature drop across it means it is choked.

Likely cause. Iced evaporator, solenoid valve fault, undercharge or choked drier.

Action. Defrost manually and repair the defrost system; or change the drier after pumping down; or find and repair the leak, then evacuate and charge. Move sensitive provisions if the room cannot be held.

Report. Chief engineer and the chief cook or cargo officer; log refrigerant added in the refrigerant record.

Examiner's note: The weak answer is "add gas". Panels want you to rule out ice and the solenoid first, and to say you would find the leak before adding refrigerant. Ozone-depleting refrigerants must not be vented, and supplies are recorded[1].

Walk-through 2: compressor trips on high pressure

Symptom. The compressor trips on HP cut-out; it resets and trips again.

Checks in order.

  1. Condenser cooling water: pump running, valves open, sea water strainer clear, sea temperature.
  2. Condenser temperature difference: compare cooling water outlet with the condensing temperature; a large difference means fouled tubes or non-condensables.
  3. Non-condensables: with the plant stopped and cooling water flowing, the condenser pressure should equal the saturation pressure at the water temperature. Higher means air is present.
  4. Overcharge after recent charging.

Likely cause. Loss of condenser cooling, fouled tubes or air in the system.

Action. Restore cooling, clean the condenser, purge non-condensables through a recovery unit.

Report. Log; refrigerant record if any gas was recovered.

Examiner's note: Never bridge the HP cut-out. Panels give that as a trap.

What should you read to revise refrigeration and air conditioning?

  • Refrigeration and Air Conditioning by A.R. Trott and T. Welch: standard text, good on cycles and components.
  • Marine Auxiliary Machinery by H.D. McGeorge: refrigeration and air conditioning chapter.
  • Introduction to Marine Engineering by D.A. Taylor: shorter overview.
  • MARPOL Annex VI, Regulation 12, and your ship's ODS equipment list and record book.
  • IACS UR M57 for ammonia, and your plant's maker manual.

Test yourself with the refrigeration MCQ set and the CES engine practice set. The books for MEO Class 4 list puts the reading in order, and the 30-day oral preparation plan schedules it.

How can you practise refrigeration answers before the oral?

Draw the cycle from memory every day for a week, then explain three faults aloud using it. Check your weak areas with the oral readiness check. Our AI voice examiner in early access asks the follow-ups an examiner would. Refrigeration questions also come up in marine engineer interview questions for reefer and container ship jobs. Compare how depth changes in MEO Class 4 vs Class 2, and pack using the oral exam day checklist. Related engine topics include pumps and pumping systems for sea water cooling, and fresh water generator for heat exchangers.

Oral practice

35 oral questions with model answers

Read the question, answer it out loud as if the examiner is across the table, then open the model answer and mark yourself honestly.

–0/35 done
  1. 1
    Core

    Draw and explain the vapour compression refrigeration cycle.

    Model answer points
    • Compressor draws low-pressure superheated vapour from the evaporator and compresses it to high pressure and temperature.
    • Condenser removes heat (to sea water or fresh water); vapour desuperheats, condenses and the liquid subcools slightly.
    • Liquid goes to the receiver, then through the filter drier, sight glass and solenoid valve.
    • Expansion valve drops pressure; some liquid flashes to vapour and the mixture becomes cold.
    • Evaporator: liquid boils, absorbing heat from the room air; vapour leaves slightly superheated.
    • High-pressure side: compressor discharge to expansion valve inlet; low-pressure side: expansion valve outlet to compressor suction.
    The examiner may follow up with
    • Why must the vapour leaving the evaporator be superheated?
    • Where is the highest temperature in the cycle?
    How did you do?
  2. 2
    Core

    What properties make a good refrigerant?

    Model answer points
    • Low boiling point at near-atmospheric pressure, so it evaporates at low temperature without deep vacuum.
    • Moderate condensing pressure.
    • High latent heat, so less mass flow is needed.
    • Non-toxic, non-flammable, chemically stable, compatible with oil and materials.
    • Easy leak detection.
    • Environmental: zero ozone depletion and low global warming potential.
    • No single refrigerant is perfect; ammonia scores well thermally but is toxic.
    The examiner may follow up with
    • Why was R12 replaced?
    How did you do?
  3. 3
    Core

    What is the function of the thermostatic expansion valve?

    Model answer points
    • Drops liquid from condensing pressure to evaporating pressure.
    • Meters liquid into the evaporator to keep a set superheat at the evaporator outlet.
    • Bulb clamped on the suction line senses outlet temperature; bulb pressure acts on top of the diaphragm against evaporator pressure and a spring.
    • More superheat opens the valve; less superheat closes it.
    • External equaliser used on evaporators with a large pressure drop.
    • It does not control room temperature; the thermostat and solenoid do.
    The examiner may follow up with
    • What happens if the bulb loses its charge?
    • What if the bulb is loose on the pipe?
    How did you do?
  4. 4
    Core

    Name the safety devices on a refrigeration compressor and what they do.

    Model answer points
    • HP cut-out: stops the compressor if discharge pressure is too high (cooling water failure, non-condensables, closed valve).
    • LP cut-out: stops it at low suction pressure (also used for automatic on-off control when the rooms are cold).
    • Oil pressure differential cut-out: stops it if oil pressure above crankcase pressure is too low, after a time delay for start-up.
    • Cooling water failure switch and high discharge temperature cut-out on many plants.
    • Relief valve or bursting disc on the condenser and receiver; relief between discharge and suction on some compressors.
    • Motor overload protection.
    The examiner may follow up with
    • Why is a time delay needed on the oil pressure cut-out?
    • Which cut-outs need manual reset?
    How did you do?
  5. 5
    Core

    The provision plant compressor tripped on HP cut-out at night. What do you do?

    Model answer points
    • Do not just reset and restart.
    • Check cooling water to the condenser: pump running, valves open, strainer clean, sea water temperature.
    • Check the condenser outlet valve and the receiver king valve are open.
    • Check for air or non-condensables (condenser pressure higher than saturation pressure at the water outlet temperature).
    • Check for overcharge (liquid level high in receiver or condenser).
    • Fix the cause, reset, start and watch pressures; change to the standby unit if needed to keep rooms cold.
    The examiner may follow up with
    • How do you purge non-condensables?
    How did you do?
  6. 6
    Core

    How do you know there is air in the system, and how do you remove it?

    Model answer points
    • Discharge pressure is higher than the saturation pressure for the condenser temperature; HP cut-out may operate.
    • Condenser feels hotter than expected; compressor discharge temperature high.
    • Stop the plant, keep cooling water running so the refrigerant condenses and air collects at the top of the condenser.
    • Compare condenser pressure with the saturation pressure at cooling water temperature.
    • Purge the non-condensables through the purge valve into a recovery unit, not straight to atmosphere.
    • Find where air came in (low side under vacuum, opened system).
    The examiner may follow up with
    • How can air get into a running system?
    How did you do?
  7. 7
    Core

    Walk me through charging refrigerant into a plant.

    Model answer points
    • Confirm correct refrigerant from the plant data and cylinder label; record the quantity.
    • Connect the cylinder to the liquid charging valve (after the receiver) with a drier in the line, and purge the hose.
    • Close the receiver outlet (king) valve and let the compressor draw liquid through the charging valve.
    • Blends (R404A, R407C) are charged as liquid so the mix does not change.
    • Watch the sight glass: clear liquid with no bubbles at full load means enough charge.
    • Close the charging valve, open the king valve, remove the cylinder, record in the log (and ODS Record Book for ODS).
    The examiner may follow up with
    • Why not charge vapour into the suction for blends?
    How did you do?
  8. 8
    Core

    How do you pump down a refrigeration system?

    Model answer points
    • Purpose: move refrigerant into the condenser and receiver so the low side can be opened.
    • Close the receiver outlet (king) valve with the compressor running.
    • The compressor draws the low side down; when suction reaches a slight positive pressure, stop the compressor (LP cut-out may be bypassed under control).
    • Close compressor suction and discharge valves as needed.
    • Do not pull the low side into deep vacuum, or air and moisture will enter through leaks.
    • After work: evacuate the opened section, open valves, restart.
    The examiner may follow up with
    • Why keep a slight positive pressure on the low side?
    How did you do?
  9. 9
    Core

    What is the effect of moisture in a refrigeration system?

    Model answer points
    • Water freezes at the expansion valve orifice, blocking flow; plant stops cooling and suction pressure falls.
    • Water with refrigerant and oil forms acids, attacking motor windings in hermetic compressors and metals.
    • Sludge forms in the oil.
    • Prevention: dry nitrogen pressure test, vacuum evacuation before charging, good drier.
    • Cure: change the filter drier, warm the expansion valve to clear ice, evacuate if badly contaminated.
    The examiner may follow up with
    • How does the moisture indicator in the sight glass work?
    How did you do?
  10. 10
    Core

    Why are evaporators defrosted and how?

    Model answer points
    • Frost from air moisture builds up on the evaporator, insulating it and blocking air flow.
    • Rooms warm up, suction pressure falls and liquid may return to the compressor.
    • Methods: electric heaters on the coil and drip tray, hot gas from the compressor discharge, or off-cycle defrost in rooms above freezing.
    • A timer starts it and a thermostat ends it; fans stop during defrost.
    • Drip tray and drain heaters prevent ice in the drain.
    The examiner may follow up with
    • How often would you defrost a meat room?
    How did you do?
  11. 11
    Core

    What is the purpose of the oil separator, and what happens if it fails?

    Model answer points
    • Compressor oil is carried with the discharge vapour.
    • The oil separator after the compressor removes most of it and returns it to the crankcase through a float valve.
    • Failure (float stuck shut): oil collects in the evaporator, reducing heat transfer, and the compressor runs short of oil; oil pressure cut-out may trip.
    • Float stuck open: hot gas passes back to the crankcase, causing foaming and heating.
    • Check crankcase oil level and the return line temperature.
    The examiner may follow up with
    • How do you get oil back from the evaporator?
    How did you do?
  12. 12
    Core

    How would you test for leaks after repairing a joint?

    Model answer points
    • Pressure the repaired section with dry nitrogen to the test pressure in the manual (never oxygen or compressed air).
    • Soap solution on joints; watch for bubbles; hold pressure and watch the gauge.
    • Release nitrogen, evacuate with a vacuum pump and hold the vacuum to prove tightness and dryness.
    • Charge refrigerant and check with an electronic detector suited to it.
    • Record work.
    The examiner may follow up with
    • Why is a halide torch not used for R134a?
    How did you do?
  13. 13
    Deeper

    Explain superheat and subcooling and why they matter.

    Model answer points
    • Superheat: vapour temperature above the saturation temperature at its pressure. At the evaporator outlet it proves no liquid is returning to the compressor.
    • Too little superheat: liquid floodback, oil dilution, compressor valve damage.
    • Too much superheat: evaporator starved, poor capacity, high discharge temperature.
    • Subcooling: liquid below its saturation temperature at condenser pressure; it reduces flash gas at the expansion valve and increases capacity.
    • Measure with a pressure gauge (convert to saturation temperature) and a thermometer on the pipe.
    The examiner may follow up with
    • How do you adjust the superheat on a TEV?
    How did you do?
  14. 14
    Deeper

    The meat room temperature is rising but the compressor is running normally. Fault-find it.

    Model answer points
    • Room load: door left open, warm cargo, failed door seals or insulation.
    • Evaporator heavily frosted: check defrost heaters, timer and drain.
    • Evaporator fan not running or reversed.
    • Room solenoid not opening (coil, thermostat setting, power).
    • TEV starving the coil: bulb charge lost, blocked strainer at the valve, ice in the orifice (moisture).
    • Low overall charge: bubbles in sight glass, low suction pressure.
    • Move perishables to another room if needed; record and fix.
    The examiner may follow up with
    • How would you prove the solenoid is opening?
    How did you do?
  15. 15
    Deeper

    What causes short cycling and how do you correct it?

    Model answer points
    • The compressor starts and stops too often, wearing contacts, motor and compressor.
    • LP cut-out differential set too narrow, so it restarts almost at once.
    • Low refrigerant charge pulling suction pressure down quickly.
    • Leaking solenoid or compressor discharge valves letting pressure equalise.
    • HP cut-out acting because of poor condenser cooling.
    • Correct the cut-out differential to the maker's setting and fix the root cause.
    The examiner may follow up with
    • How do you test an HP cut-out setting?
    How did you do?
  16. 16
    Deeper

    How is capacity controlled on a multi-cylinder reciprocating refrigeration compressor?

    Model answer points
    • Cylinder unloading: suction valves of some cylinders held open by oil-pressure-operated lifting pins, so those cylinders do no work.
    • Controlled by suction pressure: as rooms cool, suction pressure falls and more cylinders unload.
    • Also gives unloaded starting, reducing starting current.
    • Other methods: hot gas bypass, variable speed drive, on-off control with the LP switch.
    • Screw compressors use a slide valve.
    The examiner may follow up with
    • Why is unloaded starting useful on ships?
    How did you do?
  17. 17
    Deeper

    Liquid is returning to the compressor. What are the signs and dangers?

    Model answer points
    • Signs: frosting or sweating of the suction line up to the compressor, knocking, low discharge temperature, oil foaming and falling oil pressure.
    • Danger: liquid cannot be compressed; it can break valves, gaskets or connecting rods and washes oil off bearings.
    • Causes: TEV overfeeding (bulb loose or wrongly placed), evaporator fan stopped, too little superheat set, refrigerant migration to the crankcase during shutdown.
    • Fix the cause; crankcase heaters prevent migration when stopped.
    The examiner may follow up with
    • What is the purpose of a crankcase heater?
    How did you do?
  18. 18
    Deeper

    Describe a typical ship air conditioning system.

    Model answer points
    • Central air handling unit with fresh air and recirculation dampers, filters, cooling coil, heating coils and humidifier, and supply fan.
    • Direct expansion (refrigerant) or chilled water cooling coils; steam, hot water or electric heating.
    • Ducts to cabins, with local terminal units or reheaters for individual control.
    • Fire dampers where ducts pass through fire divisions; exhaust from galley, toilets and laundry.
    • Controls: temperature and humidity sensors, damper actuators.
    • Hygiene: drip trays and drains, filter cleaning, Legionella control.
    The examiner may follow up with
    • Why is the galley exhaust kept separate?
    How did you do?
  19. 19
    Deeper

    How does air conditioning control humidity in summer and winter?

    Model answer points
    • Summer: air cooled below its dew point on the cooling coil, so moisture condenses and drains; then reheated if too cold.
    • Winter: outside air is cold and dry; it is preheated, humidified with steam or water spray, then heated to supply temperature.
    • Relative humidity for comfort is kept in a moderate range by the humidistat.
    • Too much fresh air in humid climates overloads the cooling coil and raises humidity.
    The examiner may follow up with
    • What is the dew point?
    How did you do?
  20. 20
    Deeper

    What is the difference between direct and indirect refrigeration systems?

    Model answer points
    • Direct: refrigerant evaporates in coils inside the space (provision rooms, small AC units).
    • Indirect: refrigerant cools a secondary fluid (brine, glycol or chilled water), which is pumped to coolers in the spaces.
    • Indirect systems keep refrigerant in one compact plant room, reduce charge and leak risk, and suit large or many spaces (cargo holds, large AC).
    • Drawbacks: extra heat exchanger, pumps and lower efficiency.
    The examiner may follow up with
    • Why is brine strength checked?
    How did you do?
  21. 21
    Deeper

    How do you overhaul a reciprocating refrigeration compressor?

    Model answer points
    • Pump down, isolate the compressor valves, lock out the motor.
    • Recover the remaining refrigerant from the compressor and release pressure safely.
    • Open up: check suction and discharge valve plates and springs, pistons, rings, liners, bearings, shaft seal and oil pump.
    • Renew worn parts as per the maker; change oil and oil filter.
    • Reassemble, pressure test, evacuate, open valves.
    • Run and check pressures, oil pressure, temperatures; record.
    The examiner may follow up with
    • What symptoms point to leaking compressor valves?
    How did you do?
  22. 22
    DeeperMARPOL Annex VI Reg. 12

    What records must be kept for a plant using R22?

    Model answer points
    • R22 is an HCFC, an ozone-depleting substance.
    • The ship keeps a list of equipment containing ODS (in the IAPP certificate supplement).
    • An ODS Record Book for rechargeable systems.
    • Entries in kilograms for recharge (full or partial), repair or maintenance, discharge to atmosphere (deliberate or not), discharge to shore reception facilities, and supply to the ship.
    • Deliberate emissions are prohibited; recover refrigerant during maintenance.
    • Existing R22 plants may stay in service, but no new installation containing HCFCs is allowed from 1 January 2020.
    The examiner may follow up with
    • Can you install a new R22 plant today?
    How did you do?
  23. 23
    DeeperIACS UR M57

    What safety precautions apply in an ammonia refrigeration room?

    Model answer points
    • Dedicated gastight compartment, at least two access doors (except small rooms).
    • Independent negative (exhaust) ventilation of at least 30 air changes per hour.
    • Fixed ammonia detection with alarms inside and outside the room.
    • Water screens over the doors, operable from outside.
    • Independent bilge system.
    • At least two breathing apparatus and protective suits available.
    • No ammonia piping through accommodation.
    The examiner may follow up with
    • Why does water help in an ammonia leak?
    How did you do?
  24. 24
    Deeper

    What are the hazards of a halocarbon refrigerant leak in an enclosed space?

    Model answer points
    • Most halocarbon refrigerants are heavier than air; they collect in low parts and displace oxygen, causing asphyxiation without warning.
    • In flame or on hot surfaces they decompose into toxic and corrosive gases.
    • Liquid contact causes frostbite.
    • Response: alarm, no entry without breathing apparatus and enclosed space procedure, stop and isolate, ventilate, no hot work.
    The examiner may follow up with
    • What atmosphere tests would you do before entry?
    How did you do?
  25. 25
    Deeper

    What checks do you do on reefer containers on a container ship?

    Model answer points
    • Confirm each unit is plugged in and running after loading, with the set point on the manifest.
    • Regular rounds or remote monitoring: supply and return air temperatures, alarms, defrost.
    • Check plugs and sockets for damage and water; earth faults on reefer circuits.
    • Report alarms and temperature deviations promptly to the master and company as per procedures, because cargo claims follow.
    • Manage generator load when many reefers are connected.
    The examiner may follow up with
    • What would you do if a reefer shows a high temperature alarm?
    How did you do?
  26. 26
    Deeper

    What is flash gas, and how do you reduce it?

    Model answer points
    • Flash gas is liquid refrigerant that turns to vapour before the expansion valve, or the vapour formed as liquid passes through the valve.
    • Before the valve it reduces the liquid reaching the evaporator and shows as bubbles in the sight glass.
    • Causes: pressure drop in the liquid line (choked drier, long or undersized pipe, vertical lift), warm liquid line, low charge.
    • Reduce it with good subcooling (heat exchanger or liquid subcooler), clean drier, and insulated liquid lines in hot spaces.
    • Some flash at the valve is normal and unavoidable.
    The examiner may follow up with
    • How does a liquid-suction heat exchanger help?
    How did you do?
  27. 27
    Deeper

    How do you evacuate a refrigeration system before charging, and why?

    Model answer points
    • After repair and nitrogen pressure test, release the nitrogen and connect a vacuum pump to the opened section.
    • Pull a deep vacuum so moisture boils off at low temperature and air is removed.
    • Isolate the pump and watch the vacuum gauge: a rising reading means a leak or remaining moisture.
    • Repeat if needed (break the vacuum with dry nitrogen and evacuate again).
    • Then charge refrigerant and test for leaks.
    • Skipping evacuation leaves air (high head pressure) and moisture (ice at the TEV, acids).
    The examiner may follow up with
    • Why can moisture be removed by vacuum without heating?
    How did you do?
  28. 28
    DeeperRefrigeration principles; MARPOL Annex VI Reg. 12 (ODS records)

    The suction gauge shows a saturation temperature of −10 °C and the suction line at the evaporator outlet is at 4 °C. What is the superheat and what do you suspect?

    Model answer points
    • Superheat = 4 − (−10) = 14 K, measured at the evaporator outlet next to the TEV bulb.
    • Compare with the maker's setting and the plant's normal readings; if it is much higher than normal, the evaporator is underfed.
    • Check the sight glass for bubbles (undercharge), the filter drier for a temperature drop (restriction), and the TEV for ice or a lost bulb charge.
    • Check the solenoid valve is fully open.
    • If undercharged, find and repair the leak before charging; do not just top up.
    • Record any refrigerant added in the ship's refrigerant record.
    The examiner may follow up with
    • What would low superheat tell you?
    • Where exactly do you measure the suction line temperature?
    How did you do?
  29. 29
    TrapMARPOL Annex VI Reg. 12

    Should you vent refrigerant to atmosphere to clear air from a small plant?

    Model answer points
    • No. For ODS such as R22, deliberate emissions are prohibited and any loss is recorded.
    • For HFCs, venting is also poor practice and banned in many regions because of their global warming potential.
    • Purge non-condensables through a recovery unit, minimising refrigerant loss.
    • Record the quantity recovered and recharged.
    The examiner may follow up with
    • What goes in the ODS Record Book after a purge?
    How did you do?
  30. 30
    TrapMARPOL Annex VI Reg. 12; Montreal Protocol (Kigali Amendment)

    Is R134a covered by the MARPOL ODS ban?

    Model answer points
    • No. R134a is an HFC with no chlorine, so its ozone depletion potential is zero and it is not an ODS under MARPOL Annex VI Reg. 12.
    • It has high global warming potential, so it is being phased down under the Kigali Amendment to the Montreal Protocol and regional rules such as the EU F-gas Regulation, which restrict servicing and new equipment using high-GWP HFCs.
    • So do not say it is banned by MARPOL; say it is not ODS but is under climate pressure.
    • Recover and record any HFC loss in the plant records anyway; flag States and companies increasingly audit refrigerant use.
    The examiner may follow up with
    • Which refrigerants are ODS?
    How did you do?
  31. 31
    Trap

    Can you use oxygen to pressure test a refrigeration line because nitrogen is not on board?

    Model answer points
    • Never. Oxygen in contact with compressor oil under pressure can explode.
    • Compressed air is also wrong: it adds moisture and oxygen.
    • Use dry nitrogen only; if not on board, order it and isolate the section until then.
    • Then evacuate before charging.
    The examiner may follow up with
    • What test pressure would you use?
    How did you do?
  32. 32
    Trap

    The thermostatic expansion valve controls the room temperature. True?

    Model answer points
    • False. The TEV controls superheat at the evaporator outlet, so the evaporator is fed just enough liquid.
    • Room temperature is controlled by the room thermostat opening and closing the liquid solenoid valve.
    • The compressor is then controlled by the LP switch or capacity control as rooms close off.
    • Changing the TEV setting to get a colder room causes floodback or starvation.
    The examiner may follow up with
    • What controls the compressor when all rooms are satisfied?
    How did you do?
  33. 33
    Trap

    Can you top up an R407C system with vapour from the top of the cylinder?

    Model answer points
    • No. R407C is a zeotropic blend; its components boil at different temperatures.
    • Taking vapour changes the composition of both what goes in and what is left in the cylinder.
    • Charge blends as liquid, carefully, through the liquid line or with a metering device into the suction.
    • After a big leak, the maker may advise recovering the whole charge and recharging.
    The examiner may follow up with
    • What is temperature glide?
    How did you do?
  34. 34
    Trap

    A halide torch shows no leak on an R404A plant, so the system is tight. Agree?

    Model answer points
    • No. A halide torch reacts with chlorine in the refrigerant; R404A is an HFC with no chlorine, so the torch cannot see it.
    • Use an electronic detector rated for HFCs, soap solution or UV dye.
    • Look for oil stains at joints.
    • Halide torches are also an open flame, which can break down refrigerant into toxic products.
    The examiner may follow up with
    • Which detector would you use for ammonia?
    How did you do?
  35. 35
    Trap

    The compressor trips on the oil pressure cut-out just after starting. Do you bridge the switch to keep it running?

    Model answer points
    • No. Bypassing a safety cut-out risks wiping the bearings.
    • Find the cause: low oil level, oil foaming from refrigerant in the crankcase (crankcase heater off), blocked oil strainer, worn oil pump, faulty switch or wrong time delay.
    • Run the standby compressor while you investigate.
    • Test the switch setting and time delay against the maker's values.
    The examiner may follow up with
    • Why does refrigerant in the crankcase cause foaming on start?
    How did you do?

Reading answers is not the same as saying them. Our AI voice examiner asks these out loud, listens to your answer, asks the follow-up and marks you against the rule. Join early access or try the free timed mock oral drill.

Frequently asked questions

What is the vapour compression refrigeration cycle?

Refrigerant evaporates at low pressure in the evaporator, absorbing heat from the room. The compressor raises the vapour to high pressure and temperature, the condenser rejects that heat to cooling water and the vapour condenses, and the expansion valve drops the pressure back to the evaporator. The cycle then repeats.

Is R22 banned on ships?

New installations containing HCFCs such as R22 have been prohibited from 1 January 2020 under MARPOL Annex VI Reg. 12. Existing R22 plants may stay in service, but deliberate emissions are banned and recharges and losses go in the ODS Record Book. Many owners are converting or replacing them.

Is R404A an ozone-depleting substance?

No. R404A, R134a, R407C and R507 are HFCs with no chlorine, so they do not deplete ozone and are not controlled by MARPOL Annex VI Reg. 12. They do have high global warming potential and are being phased down under the Kigali Amendment and regional rules.

What does the thermostatic expansion valve control?

It controls the superheat of the vapour leaving the evaporator by metering liquid refrigerant into it. The sensing bulb on the evaporator outlet and the evaporator pressure act on the valve diaphragm against a spring. Room temperature is controlled by the thermostat and solenoid valve.

What causes high head pressure in a refrigeration plant?

Common causes are air or other non-condensables in the condenser, fouled condenser tubes, low cooling water flow or high sea water temperature, and overcharge. Check cooling water first, then the condenser temperature difference, and purge non-condensables if needed.

What safety cut-outs does a refrigeration compressor have?

High-pressure cut-out, low-pressure cut-out (often also used for capacity control), oil pressure differential cut-out, cooling water failure switch and motor overload protection. Many plants also have a high discharge temperature cut-out. Relief valves or bursting discs protect the condenser and receiver.

Why is a filter drier fitted?

Moisture in the system freezes at the expansion valve, forms acids with the oil and refrigerant, and damages the compressor. The drier absorbs moisture and traps dirt in the liquid line. Change it when the moisture indicator shows wet or it causes a pressure drop.

How do you detect refrigerant leaks?

Use an electronic leak detector suited to the refrigerant, soapy water on joints, or UV dye where fitted. Watch for oil stains at joints because oil travels with the refrigerant. Halide lamps work only on chlorine-containing refrigerants and are not used for HFCs.

Why is nitrogen used to pressure test refrigeration systems?

Dry nitrogen is inert and contains no moisture. Oxygen can react violently with compressor oil and cause an explosion, and compressed air brings in moisture. After the pressure test the system is evacuated with a vacuum pump before charging.

What is an ODS Record Book?

A record book required under MARPOL Annex VI Reg. 12 for ships with rechargeable systems containing ozone-depleting substances. It records, in kilograms, recharges, repairs, discharges (deliberate or not), deliveries to shore and supplies to the ship. It is checked during surveys and port State inspections.

Why is ammonia plant in a separate room?

Ammonia is toxic, corrosive and flammable in some concentrations. IACS UR M57 requires a dedicated gastight room with strong independent ventilation, fixed ammonia detectors, water screens over the doors and breathing apparatus nearby. Ammonia pipes must not pass through accommodation.

Which book should I use for refrigeration orals?

Refrigeration and Air Conditioning by A.R. Trott and T. Welch is the standard. Marine Auxiliary Machinery by H.D. McGeorge gives the marine-specific view in one chapter. Add MARPOL Annex VI Reg. 12 for the regulatory questions.

Sources 4 documents

Each number in the text links to the source below. Labels show the type of source; see our editorial policy.

  1. Official REMPEC (IMO/UNEP Regional Centre), MARPOL Annex VI regulations presentation, 2020 · 26 November 2020
  2. Reported Turk Loydu TL-R M (January 2023), reproducing IACS UR M57 Use of ammonia as a refrigerant · 1 January 2023
  3. Official TEAP Manual Part A (Consolidated Rev. 1, 1 May 2015), Chapter III, Tables III/0-1 and III/0-2 · 1 May 2015
  4. Official MIN 654 (M) Engineering and Electro-technical Officer Oral Exam Syllabus, Amendment 1 (April 2026) · 21 April 2026

Where should you go next?

  • Oral topics14 pages: examiner questions with model answer points, deck and engine
  • Question banks7 pages: free MCQ sets with answers and explanations
  • CoC exam guides16 pages: every oral and written exam, authority by authority
  • Free tools4 pages: mock oral drill, lights trainer, sea-time calculator, practice tests
Exam Prep DeskMaritime exam researchers

We write from the conventions (STCW, COLREG, SOLAS, MARPOL), the authorities' own notices and published syllabi, and cite the source for every fee, rule and date. We are independent and not linked to any maritime administration or test provider. Found an error? It matters at sea: tell us and see how we correct · Disclaimer.

Related guides

AI voice mock oral

Say it out loud before the examiner asks.

Our examiner asks CoC oral questions by rank and function, listens to your answer, asks the follow-up and scores you against the rule. Early access is open for India first.

  • Deck and engine, every rank
  • Answers referenced to the conventions
  • Independent, not linked to any authority
WhatsApp us